Tanjia Street, Weiyang District, Xi'an City, Shaanxi Province, China

Siemens SITRANS FCT040 Coriolis Flow Transmitter

Home/Siemens SITRANS FCT040 Coriolis Flow Transmitter

Siemens SITRANS FCT040 Coriolis Flow Transmitter

$750.00

SIEMENS

FCT040 is the advanced transmitter, offering a wider range of application solutions with improved performance. The user can select additional measurements and functions at time of ordering to include concentration (fraction), viscosity, batch control and heat calculation.

 

Description

Overview---SITRANS FCT040

SITRANS FCT040 is the advanced transmitter, offering a wider range of application solutions with improved performance. The user can select additional measurements and functions at time of ordering to include concentration (fraction), viscosity, batch control and heat calculation.

The FCT040 transmitter is available in compact or remote design and can be combined with all SITRANS FC sensors.

Make the selection within the complete SITRANS FC ordering code. Select spare transmitters using the SITRANS FC ordering code, but don't select any sensor.

Function

Measurement of heat quantity
  • Order code: S11

This function calculates the total fuel calorific value of the measured fluid. Engineers can either use a constant value of the calorific value of the fluid or rely on an additional device like a gas chromatograph to provide the instantaneous calorific value through the analog input of the FCT040 transmitter. Then, we calculate the total calorific energy of the fluid based on its flow.

For questions regarding a specific application, contact your regional Siemens Measurement Intelligence team.

Tube health check
  • Order code: S12

Tube health check monitors key diagnostics, including tube stiffness, driver and pickups. Self-verification alerts to potential performance issues due to unplanned process events, for example gas or vapor breakout, or solid deposits building up in the tubes. The user defines verification frequency and alarm behavior. Verification results indicate whether preventive maintenance action is required.

Petroleum measurement function
  • Order code: S14

The Net Oil Computing (NOC) function provides real-time measurements of water cut and includes American Petroleum Institute (API) correction according to API MPMS Chapter 11.1.

Oil sometimes contains entrained gas. SITRANS FC flowmeters measure the density of the combined emulsion oil and gas, which is lower than the oil density. The NOC function includes a Gas Void Fraction (GVF) parameter to be set.

Viscosity function
  • Order code: S15

Viscosity is sometimes can use to activate other processes like fluid heating systems.

Engineers calculate the viscosity estimation by comparing the measured pressure loss with the calculated value between two points of the pipe. To use this function, we need a differential pressure transmitter. We connect its output to the analog input of the FCT040. Through an iteration process, we determine a viscosity value.

Standard concentration measurement
  • Order code: S16

Used for concentration measurements of emulsions or suspensions when density of the fluid involved depends only on temperature.

The standard concentration measurement can be used for many low-concentration solutions if there is only minor interaction between the liquids, or if the miscibility is negligible.

SITRANS FCT040      SITRANS FCT040 To obtain the most competitive quote, please contact our ANTLETS team.

Discover more from SIEMENS

Subscribe to get the latest posts sent to your email.

Additional information

Brand

SIEMENS

communication

Hart, Modbus, Profibus PA

Function

Batching function and Viscosity function

Dynamic Pressure Compensation

For consistently accurate and stable measurement even with significant fluctuations in operating pressures

Tube health check and key diagnostics

For inline meter verification without disturbing running measurements

Reviews

There are no reviews yet.

Be the first to review “Siemens SITRANS FCT040 Coriolis Flow Transmitter”

Your email address will not be published. Required fields are marked *